Mitsubishi - 5.0kW
5.0kW
PCA-RP50GACooling Only
R407c Ceiling Suspended System
Model Info
R407c Compatible
  • Indoor unit designed for direct ceiling suspension
  • Flush to wall installation for concealment of service connections
  • Electronic control includes learning defrost, fault finding diagnostics, low ambiet fan speed control and anti-phase/single phase protection
PCA-RP50GAPU-P50VGAAPAR-21MAA Controller
Hover your mouse over the red icons below to view a description of each feature:
Swing Vane modeAuto Vane Shutter - when unit is switched off the vane automatically closesLong Airflow Mode - particularly suitable for use in long, narrow spacesOptimised Rotary or Scroll compressorAuto-RestartQuiet OperationStandard filterOptional drain lift pumpDouble thermostat function - control the temp via a sensor in the controller or the unit (wired remote controllers only)
 
Dimensions
PCA-RP50GA (Click to enlarge).
PCA-RP50GA
PU-P50VGAA (Click to enlarge).
PU-P50VGAA
PCA-RP50GA Indoor Unit
Capacity (kW): 
Cooling (Nominal)5.35
Cooling (UK)4.80
SHF R407c (Nominal)0.72
Width - mm1000
Depth - mm680
Height - mm210
Weight - kg27
Airflow (m3/min) - Lo-Mi1-Mi2-Hi10-11-12-13
Noise (dBA) - Lo-Mi1-Mi2-Hi37-38-40-42
Pipe Size Gas mm (in)15.88 (5/8)
Pipe Size Liquid mm (in)9.52 (3/8)
Electrical SupplyFed by Outdoor Unit
PhaseSingle
Fuse Rating (BS88) - HRC (A)6
Interconnecting Cable No. Cores4
Remote Controller RefPAR-21MAA
PU-P50VGAA Outdoor Unit
Width - mm900
Depth - mm330 + 20
Height - mm855
Weight - kg74
Noise (dBA) 48
Electrical Supply220-240v, 50Hz
PhaseSingle
Fuse Rating (BS88) - HRC (A)16
SystemPower Input (kW) - Cooling (Nominal)2.35
SystemPower Input (kW) - Cooling (UK)2
Starting Current (A)62
SystemRunning Current (A) - Cooling10.67
Mains Cable No. Cores3
Max Pipe Length (m)40
Max Height Difference (m)40
Charge (kg) - 20m2.6
Powered by Enable Software