PCA-RP71HAHeat Pump
R407c Stainless Steel Ceiling Suspended System
- High performance oil mist filter
- Easy maintenance - fan casing can be separated into different sections allowing easy cleaning. The drain pan can also be cleaned easily on-site as the pipe connector can be quickly removed
- Optional decoration covers
The PCA-RP-HA series is a ceiling suspended unit ideal for use in kitchen environments. The external casing is made of durable stainless steel that is resistant to oil and smoke, ensuring that the unit can be easily cleaned at all times.
Hover your mouse over the red icons below to view a description of each feature:
PCA-RP71HA
(Click to enlarge).PUH-P71VGAA
(Click to enlarge).| Capacity (kW): | |
| Heating (Nominal) | 9.20 |
| Cooling (Nominal) | 7.50 |
| Heating (UK) | 7.80 |
| Cooling (UK) | 6.75 |
| SHF R407c (Nominal) | 0.72 |
| Width - mm | 1136 |
| Depth - mm | 650 |
| Height - mm | 280 |
| Weight - kg | 41 |
| Airflow (m3/min) - Lo-Hi | 17-19 |
| Noise (dBA) - Lo-Hi | 34-38 |
| Pipe Size Gas mm (in) | 15.88 (5/8) |
| Pipe Size Liquid mm (in) | 9.52 (3/8) |
| Electrical Supply | Fed by Outdoor Unit |
| Phase | Single |
| Fuse Rating (BS88) - HRC (A) | 6 |
| Interconnecting Cable No. Cores | 4 |
| Width - mm | 900 |
| Depth - mm | 330 + 20 |
| Height - mm | 855 |
| Weight - kg | 79 |
| Noise (dBA) (Heating /Cooling) | 51 /49 |
| Electrical Supply | 220-240v, 50Hz |
| Phase | Single |
| Fuse Rating (BS88) - HRC (A) | 32 |
| SystemPower Input (kW) - Heating (Nominal) | 3.41 |
| SystemPower Input (kW) - Cooling (Nominal) | 3.36 |
| SystemPower Input (kW) - Heating (UK) | 3.03 |
| SystemPower Input (kW) - Cooling (UK) | 2.86 |
| Starting Current (A) | 93 |
| SystemRunning Current (A) - Heating / Cooling | 6.06 / 5.72 |
| Mains Cable No. Cores | 3 |
| Max Pipe Length (m) | 50 |
| Max Height Difference (m) | 50 |
| Charge (kg) - 30m | 3.3 |