PEH-RP200MYAPower Inverter Heat Pump
R410A Large Capacity Ceiling Concealed Ducted System
- Twin, triple or quadruple configurations on one outdoor unit, utilising Mr Slim indoor units
- Static pressure of up to 150Pa
Advanced inverter technology makes the Mr Slim Power Inverter the number one choice for improving comfort. They provide energy savings of up to 70% annually when compared to a previous non-inverter model. Operating noise has also been reduced thanks to improvements in fan design, while existing pipe work is reusable for easier maintenance and installation.
Hover your mouse over the red icons below to view a description of each feature:
PEH-RP200MYA
(Click to enlarge).PUHZ-RP200MYA
(Click to enlarge).| Capacity (kW): | |
| Heating (Nominal) (Low - High) | 22.4 (10.0 - 25.0) |
| Cooling (Nominal) (Low - High) | 19.0 (10.0 - 22.4) |
| Heating (UK) (Low - High) | 19.05 (8.5 - 21.25) |
| Cooling (UK) (Low - High) | 17.1 (9.0 - 21.15) |
| SHF R410A (Nominal) | 0.75 |
| COP / EER (Nominal) | 3.14 / 2.74 |
| Energy Label Heating / Cooling | D / D |
| Width - mm | 1380 |
| Depth - mm | 650 |
| Height - mm | 428 |
| Weight - kg | 70 |
| External Static Pressure Pa - Lo-Hi | 50-150 |
| Noise (dBA) | 49 |
| Pipe Size Gas mm (in) | 28.58 (1 1/8) |
| Pipe Size Liquid mm (in) | 9.52 (3/8) |
| Electrical Supply | 380-415v, 50Hz |
| Phase | 3 |
| Fuse Rating (BS88) - HRC (A) | 6 |
| Power Input (kW) - Heating (Nominal) | 0.65 |
| Power Input (kW) - Cooling (Nominal) | 0.65 |
| Power Input (kW) - Heating (UK) | 0.58 |
| Power Input (kW) - Cooling (UK) | 0.58 |
| Starting Current (A) | 5 |
| Running Current (A) - Heating / Cooling | 1.12 / 1.12 |
| Interconnecting Cable No. Cores | 3 |
| Mains Cable No. Cores | 5 |
| Remote Controller Ref | PAR-21MAA |
 | PUHZ-RP200MYA Outdoor Unit |  |  |
| Width - mm | 900 |
| Depth - mm | 750 |
| Height - mm | 1798 |
| Weight - kg | 198 |
| Noise (dBA) (Heating /Cooling) | 56 /55 |
| Electrical Supply | 380-415v, 50Hz |
| Phase | 3 |
| Fuse Rating (BS88) - HRC (A) | 40 |
| Power Input (kW) - Heating (Nominal) | 6.48 |
| Power Input (kW) - Cooling (Nominal) | 6.26 |
| Power Input (kW) - Heating (UK) | 5.77 |
| Power Input (kW) - Cooling (UK) | 5.32 |
| Starting Current (A) | 5 |
| Running Current (A) - Heating / Cooling | 10.4 / 10 |
| Mains Cable No. Cores | 5 |
| Max Pipe Length (m) | 70 |
| Max Height Difference (m) | 40 |
| Charge (kg) - 30m | 10.5 |