Mitsubishi - 10.0kW
10.0kW
PKA-RP100FALPower Inverter Heat Pump
R410A Wall Mounted System
Model Info
Qualified for Energy Technology ListR410A CompatiblePower Inverter
  • Adjustable louvres for uniform air distribution
  • Internal pipe connection to wall mounted unit for easy and neat installation

Advanced inverter technology makes the Mr Slim Power Inverter the number one choice for improving comfort. They provide energy savings of up to 70% annually when compared to a previous non-inverter model. Operating noise has also been reduced thanks to improvements in fan design, while existing pipe work is reusable for easier maintenance and installation.

PKA-RP100FALPUHZ-RP100YHAPKA-RP Controller
Hover your mouse over the red icons below to view a description of each feature:
Swing Vane modeAuto Vane Shutter - when unit is switched off the vane automatically closesInfra-red remote controllerOptimised Rotary or Scroll compressorInverter control - adjusts performance to economically match the demand for heating or coolingAuto-RestartQuiet OperationAuto-ChangeoverHot Start - draught preventionFactory charged refrigerant up to 30mStandard filterOptional drain lift pumpReplace Technology Available
 
Dimensions
PKA-RP100FAL (Click to enlarge).
PKA-RP100FAL
PUHZ-RP100YHA (Click to enlarge).
PUHZ-RP100YHA
PKA-RP100FAL Indoor Unit
Capacity (kW): 
Heating (Nominal) (Low - High)11.20 (4.50 - 14.00)
Cooling (Nominal) (Low - High)10.00 (4.90 - 11.40)
Heating (UK) (Low - High)9.50 (3.85 - 11.90)
Cooling (UK) (Low - High)9.00 (4.40 - 10.25)
SHF R410A (Nominal)0.71
COP / EER (Nominal)3.45 / 3.41
Energy Label Heating / CoolingB / A
Width - mm1680
Depth - mm235
Height - mm340
Weight - kg28
Airflow (m3/min) - Lo-Hi22-28
Noise (dBA) - Lo-Hi41-46
Pipe Size Gas mm (in)15.88 (5/8)
Pipe Size Liquid mm (in)9.52 (3/8)
Electrical SupplyFed by Outdoor Unit
PhaseSingle
Fuse Rating (BS88) - HRC (A)6
Interconnecting Cable No. Cores4
PUHZ-RP100YHA Outdoor Unit
Width - mm950
Depth - mm330+30
Height - mm1350
Weight - kg135
Noise (dBA) (Heating /Cooling)51 /49
Electrical Supply380-415v, 50Hz
Phase3
Fuse Rating (BS88) - HRC (A)16
SystemPower Input (kW) - Heating (Nominal)3.25
SystemPower Input (kW) - Cooling (Nominal)2.93
SystemPower Input (kW) - Heating (UK)2.89
SystemPower Input (kW) - Cooling (UK)2.49
Starting Current (A)5
SystemRunning Current (A) - Heating / Cooling4.85 / 4.31
Mains Cable No. Cores3
Max Pipe Length (m)75
Max Height Difference (m)30
Charge (kg) - 30m5