Mitsubishi - 3.5kW
3.5kW
PLA-RP35BAPower Inverter Heat Pump
R410A 4-Way Blow Ceiling Cassette System
Model Info
R410A CompatiblePower Inverter
  • Airflow controllable for ceiling heights up to 4.2m, with automatic adjustment of fan speed
  • Reduced draft air distribution, with independent vane control
  • Filter lowering operation down to 4m (optional PLP-6BAJ grille required)
  • Optional 'I See Sensor' for energy saving and smooth temperature control throughout the room
Advanced inverter technology makes the Mr Slim Power Inverter the number one choice for improving comfort. They provide energy savings of up to 70% annually when compared to a previous non-inverter model. Operating noise has also been reduced thanks to improvements in fan design, while existing pipe work is reusable for easier maintenance and installation.
PLA-RP35BAPUHZ-RP35VHA4PAR-21MAA Controller
Hover your mouse over the red icons below to view a description of each feature:
Swing Vane modeAuto Vane Shutter - when unit is switched off the vane automatically closesOptimised Rotary or Scroll compressorInverter control - adjusts performance to economically match the demand for heating or coolingAuto-RestartQuiet Operation72 different airflow patterns - 2, 3 or 4 way dischargeHigh Ceiling Compatibility through wide flow air outletsAuto-ChangeoverHot Start - draught preventionFactory charged refrigerant up to 30mStandard filterOptional high efficiency filterDrain lift pump as standardFresh air knockoutDouble thermostat function - control the temp via a sensor in the controller or the unit (wired remote controllers only)Ceiling soiling preventionReplace Technology AvailableRefrigerant Volume Check FunctionI-See SensorDuty Standby Operation
 
Dimensions
PLA-RP35BA (Click to enlarge).
PLA-RP35BA
PUHZ-RP35VHA4 (Click to enlarge).
PUHZ-RP35VHA4
PLA-RP35BA Indoor Unit
Capacity (kW): 
Heating (Nominal) (Low - High)4.10 (1.60 - 5.20)
Cooling (Nominal) (Low - High)3.60 (1.60 - 4.50)
Heating (UK) (Low - High)3.50 (1.35 - 4.40)
Cooling (UK) (Low - High)3.30 (1.45 - 4.15)
SHF R410A (Nominal)0.84
COP / EER (Nominal)3.66 / 3.36
Energy Label Heating / CoolingA / A
Width (grille)  - mm840 (950)
Depth (grille)  - mm840 (950)
Height (grille)  - mm258 (35)
Weight (grille)  - kg22 (6)
Airflow (m3/min) - Lo-Mi1-Mi2-Hi11-12-13-15
Noise (dBA) - Lo-Mi1-Mi2-Hi27-28-29-31
Pipe Size Gas mm (in)12.7 (1/2)
Pipe Size Liquid mm (in)6.35 (1/4)
Electrical SupplyFed by Outdoor Unit
PhaseSingle
Fuse Rating (BS88) - HRC (A)6
Interconnecting Cable No. Cores4
Grille RefPLP-6BA GRILLE
PUHZ-RP35VHA4 Outdoor Unit
Width - mm800
Depth - mm300 + 23
Height - mm600
Weight - kg42
Noise (dBA) (Heating /Cooling) - Lo-Hi46 /41-44
Electrical Supply220-240v, 50Hz
PhaseSingle
Fuse Rating (BS88) - HRC (A)16
SystemPower Input (kW) - Heating (Nominal)1.12
SystemPower Input (kW) - Cooling (Nominal)1.07
SystemPower Input (kW) - Heating (UK)1
SystemPower Input (kW) - Cooling (UK)0.91
Starting Current (A)5
SystemRunning Current (A) - Heating / Cooling5.15 / 4.98
Mains Cable No. Cores3
Max Pipe Length (m)50
Max Height Difference (m)30
Charge (kg) - 30m2.5