PCA-RP50KAStandard Inverter Heat Pump
R410A Ceiling Suspended System
- Indoor unit designed for direct ceiling suspension
- Flush to wall installation for concealment of service connections
The new Standard Inverter range provides inverter solutions for customers who want all the benefits that inverters offer, but do not have the budget available for the more expensive Power Inverter range.
Hover your mouse over the red icons below to view a description of each feature:
PCA-RP50KA
(Click to enlarge).SUZ-KA50VA2
(Click to enlarge).| Capacity (kW): | |
| Heating (Nominal) (Low - High) | 5.50 (0.90 - 6.60) |
| Cooling (Nominal) (Low - High) | 5.00 (1.10 - 5.60) |
| Heating (UK) (Low - High) | 4.55 (0.75 - 5.50) |
| Cooling (UK) (Low - High) | 4.95 (1.10 - 5.55) |
| SHF R410A (Nominal) | 0.79 |
| COP / EER (Nominal) | 3.22 / 3.01 |
| Energy Label Heating / Cooling | C / B |
| Width - mm | 960 |
| Depth - mm | 680 |
| Height - mm | 230 |
| Weight - kg | 25 |
| Airflow (m3/min) - Lo-Mi1-Mi2-Hi | 10-11-13-15 |
| Noise (dBA) - Lo-Mi1-Mi2-Hi | 32-34-37-40 |
| Pipe Size Gas mm (in) | 12.7 (1/2) |
| Pipe Size Liquid mm (in) | 6.35 (1/4) |
| Electrical Supply | Fed by Outdoor Unit |
| Phase | Single |
| Fuse Rating (BS88) - HRC (A) | 6 |
| Interconnecting Cable No. Cores | 4 |
| Width - mm | 840 |
| Depth - mm | 330 |
| Height - mm | 850 |
| Weight - kg | 53 |
| Noise (dBA) (Heating /Cooling) | 55 /53 |
| Electrical Supply | 220-240v, 50Hz |
| Phase | Single |
| Fuse Rating (BS88) - HRC (A) | 20 |
| SystemPower Input (kW) - Heating (Nominal) | 1.71 |
| SystemPower Input (kW) - Cooling (Nominal) | 1.66 |
| SystemPower Input (kW) - Heating (UK) | 1.56 |
| SystemPower Input (kW) - Cooling (UK) | 1.33 |
| Starting Current (A) | 6.75 |
| SystemRunning Current (A) - Heating / Cooling | 6.72 / 7.12 |
| Mains Cable No. Cores | 3 |
| Max Pipe Length (m) | 30 |
| Max Height Difference (m) | 30 |
| Charge (kg) - 7m | 1.6 |