The new City Multi Zubadan heat pumps achieve and excellent heating performance even when the outdoor air temperature is as low as -25 degrees C.
![]() |
![]() | Dimensions | ![]() | ![]() |
![]() | PUHY-HP200YHM-A | ![]() | ![]() |
| Capacity (kW): | |
| Heating (Nominal) | 25.0 |
| Cooling (Nominal) | 22.4 |
| Heating (UK) | 26.5 |
| Cooling (UK) | 21.3 |
| Power Input (kW) Heating (Nominal) | 6.52 |
| Power Input (kW) Cooling (Nominal) | 6.4 |
| Power Input (kW) Heating (UK) | 10.43 |
| Power Input (kW) Cooling (UK) | 3.97 |
| Max No. of Connectable Indoor Units | 17 |
| Airflow(m3/min) | 225 |
| Noise (dBA) | 56 |
| Width - mm | 920 |
| Depth - mm | 760 |
| Height - mm | 1710 |
| Weight - kg | 220 |
| Electrical Supply | 380-415v, 50Hz |
| Phase | 3 |
| Mains Cable No. Cores | 4 + earth |
| Starting Current (A) | 8 |
| Running Current (A) - Heating | 10 |
| Running Current (A) - Cooling | 9.8 |
| Fuse Rating (BS88) - HRC (A) | 32 |
![]() | Piping Restrictions | ![]() | ![]() |
| Total Piping Length (m) | 300 |
| Furthest Piping Length (m) | 150 |
| Furthest Piping Length after 1st Branch (m) | 40 |
| Between Indoor and Outdoor Units - Height (m) | 50 |
| Between Indoor and Indoor Units - Height (m) | 15 |