PLA-RP100BA3Zubadan Inverter Heat Pump
R410A 4-Way Blow Ceiling Cassette System
- Optional 'I See Sensor' for energy saving and smooth temperature control throughout the room
- Airflow controllable for ceiling heights up to 4.2m, with automatic adjustment of fan speed
- Reduced draft air distribution, with independent vane control
- Filter lowering operation down to 4m (optional PLP-6BAJ grille required)
The new Mr Slim Zubadan Inverter heat pumps achieve an excellent heating performance even when the outdoor air temperature is as low as -25 degrees C.
Hover your mouse over the red icons below to view a description of each feature:
PLA-RP100BA3
(Click to enlarge).PUHZ-HRP100YHA2
(Click to enlarge).| Capacity (kW): | |
| Heating (Nominal) (Low - High) | 11.20 (4.50 - 14.00) |
| Cooling (Nominal) (Low - High) | 10.00 (4.90 - 11.40) |
| Heating (UK) (Low - High) | 11.10 (4.45 - 13.85) |
| Cooling (UK) (Low - High) | 9.20 (4.50 - 10.50) |
| SHF R410A (Nominal) | 0.74 |
| COP / EER (Nominal) | 4.31 / 4 |
| Energy Label Heating / Cooling | A / A |
| Width (grille) - mm | 840 (950) |
| Depth (grille) - mm | 840 (950) |
| Height (grille) - mm | 298 (35) |
| Weight (grille) - kg | 26 (6) |
| Airflow (m3/min) - Lo-Mi1-Mi2-Hi | 20-23-26-30 |
| Noise (dBA) - Lo-Mi1-Mi2-Hi | 32-34-37-40 |
| Pipe Size Gas mm (in) | 15.88 (5/8) |
| Pipe Size Liquid mm (in) | 9.52 (3/8) |
| Electrical Supply | Fed by Outdoor Unit |
| Phase | Single |
| Fuse Rating (BS88) - HRC (A) | 6 |
| Interconnecting Cable No. Cores | 4 |
| Grille Ref | PLP-6BA GRILLE |
 | PUHZ-HRP100YHA2 Outdoor Unit |  |  |
| Width - mm | 950 |
| Depth - mm | 330+30 |
| Height - mm | 1350 |
| Weight - kg | 134 |
| Noise (dBA) (Heating /Cooling) - Lo-Hi | 52 /48-51 |
| Electrical Supply | 380-415v, 50Hz |
| Phase | 3 |
| Fuse Rating (BS88) - HRC (A) | 16 |
| SystemPower Input (kW) - Heating (Nominal) | 2.6 |
| SystemPower Input (kW) - Cooling (Nominal) | 2.5 |
| SystemPower Input (kW) - Heating (UK) | 3.77 |
| SystemPower Input (kW) - Cooling (UK) | 2.13 |
| Starting Current (A) | 3 |
| SystemRunning Current (A) - Heating / Cooling | 4.86 / 4.69 |
| Mains Cable No. Cores | 5 |
| Max Pipe Length (m) | 75 |
| Max Height Difference (m) | 30 |
| Charge (kg) - 30m | 5.5 |